Especificaciones





























































































Main
GamaComPact
Product nameComPact NS
Range of producComPact NS630b…1600
Device short nameCompact NS800H
Tipo de producto o componenteCircuit breaker
Device applicationDistribution
Number of poles3P
Protected poles description3D
(In) rated current up to 65 °C800 A at 50 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeCA
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
utilisation categoryCategory B
[Icu] rated ultimate short-circuit breaking capacity42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelH 70 kA 415 V AC
Trip unit nameMicroLogic 2.0
Trip unit technologyElectrónica
Trip unit protection functionsLI
control typeToggle
Rotary handle
Circuit breaker mounting modeFijo





















































































































Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current19.2 kA 1 s conforming to IEC 60947-2
Mechanical durability10000 cycles
Electrical durability2000 cycles at 690 V In
4000 cycles at 690 V In/2
5000 cycles at 440 V In
6000 cycles at 440 V In/2
Power losses15 W
mounting supportBackplate
Upside connectionFront
downside connectionFront
Connection pitch70 mm
Protection typeL : for overload protection (long time)
I : for instantaneous short-circuit protection
Trip unit rating800 A at 50 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range0.4…1 x In
Long-time protection delay adjustment type trAdjustable 9 settings
[tr] long-time protection delay adjustment range12.5…600 s at 1.5 x Ir
0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
thermal memory20 mn
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5…10 x Ir
earth-leakage protectionSin
Zone selective interlocking ZSISin
Auxiliary contact composition1 NO/NC
Local signalling4 LEDs (red) for fault indication
1 LED (yellow) for overload
Width (W)210 mm
Height (H)327 mm
Depth (D)147 mm
Peso neto14 kg









































Medio ambiente
StandardsEN/IEC 60947-2
product certificationsASEFA
ASTA
Pollution degree3 conforming to IEC 60947
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to EN 50102
ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Humedad relativa0…95 %
Altitud de funcionamiento0…2000 m without derating
2000 m…5000 m with derating